Main specification
● Number of Inputs :1 point
● Input type : ※See the Input Range Code for the input range.
1) Thermocouple : K, J, T, S, R, E, B, N, W5Re/W26Re, U, L, PLII
2) RTD: Pt100 or JPt100
3) DC voltage: 0 to 5V dc, 1 to 5V dc
4) DC current: 0 to 20mA dc, 4 to 20mA dc ※ A 250Ω external resistor is required.
● Sampling time: 0.5 sec.
● Measurement accuracy:±(0.3% of displayed value+1 digit) ※Depends on the input and the range.
● Output (OUT1)
1) Relay contact output : 1a contact
2) Voltage pulse output for SSR driving: 0/12V dc
3) Current output : 4 to 20mA dc
4) Triac trigger output: Trigger method – Zero cross method
5)Triac output: Rating 0.5A
♦Specification of Options♦
● Alarm outputs (max.2 points): Temperature alarm, Heater break alarm, and Control loop break alarm
● Auxiliary outputs: Temperature alarm output, Relay contact output
● Analog output: 0 to 20mA dc, 4 to 20mA dc
※Output type can be selected from PV, SV, deviation, or MV
● External contact input: RUN/STOP switching or SV1/SV2 switching
● CT input for Heater break alarm (max. 1 point)
♦General Specification♦
● Power supply voltage (Rating): 100 to 240Vac / 24Vac / 24Vdc
● Ambient temperature: 0 to 50°C
● Weight:
CB103 Approx.170g
CB403 Approx.250g
CB903 Approx.340g
● Safety standards: UL UL61010-1
cUL CAN/CSA-22.2 NO.61010-1
CE Marking: Low Voltage Directive (LVD) EN61010-1
EMC Directive EN61326-1