02-805-5888   info@summitindustech.com

Heater break alarm module
HBA-T120 / HBA-T130

Brand : RKC
Category : Controllers
SKU : HBA-T120 / HBA-T130 Heater break alarm module

Main features

HBA-T120 (for a single phase power control system)

Automatic setting of load current using a built-in MCU. Used for phase control and zero cross control by a power controller.

Supported CT: MCTL-6-P-N (load current up to 30A), MCTL-12-S56-10L-N (load current up to 100A)

※Available for relay contact or SSR drive control systems

HBA-T130 (for a three phase power control system)

Automatic setting of load current using a built-in MCU. Used for phase control and zero cross control applications by a three phase power controller.

Supported CT: MCTL-6-P-N (load current up to 30A), MCTL-12-S56-10L-N (load current up to 100A)

※Two CTs are used for three phase control.

※Available for relay contact or SSR drive control systems

Main specification

HBA-T120 (for a single phase power control system)

  • Input type:

HBA-T120□-5  MCTL-6-P-N
HBA-T120□-30  MCTL-6-P-N
HBA-T120□-100  MCTL-12-S56-10L-N

  • Detectable load current:

HBA-T120□-5  1 to 5A (Rating: 5A)
HBA-T120□-30  6 to 30A (Rating: 30A)
HBA-T120□-100  20 to 100A (Rating: 100A)

  • Settable range: 0 to 30% of the rated value of the device set in rate of current decrease (0 to 15%×2 of alarm set value)
  • Accuracy of load setting: within ±3% of load set value
  • Accuracy of alarm setting: within ±3% of load set value
    ※Accuracy is not guaranteed when the load voltage is 30% or less of the rating.

HBA-T130 (for a three phase power control system)

  • Input type:

HBA-T130□-5  MCTL-6-P-N
HBA-T130□-30  MCTL-6-P-N
HBA-T130□-100  MCTL-12-S56-10L-N

  • Detectable load current:

HBA-T130□-5  1 to 5A (Rating: 5A)
HBA-T130□-30  6 to 30A (Rating: 30A)
HBA-T130□-100  20 to 100A (Rating: 100A)

  • Settable range: 0 to 30% of the rated value of the device set in rate of current decrease (0 to 15%×2 of alarm set value)
  • Accuracy of load setting: within ±3% of rated capacity of alarm unit
  • Accuracy of alarm setting: within ±3% of rated capacity of alarm unit
    ※Accuracy is not guaranteed when the load voltage is 30% or less of the rating.

  • Alarm output: 1 point, Relay contact, 1a contact
  • Supply voltage: 100 to 220V, 50/60Hz
  • Power consumption: 1.2VA or less
  • Operating ambient temperature: 0 to 50°C

External dimensions

Models

Share